UPS Reference Chart
Relations Between UPS Output Capacity and Discharge Time (minutes)
Conditions:
1. Ambient temperature at 77oF (25oC)
2. Nominal battery voltage at 48V and 96V
3. Minimum voltage 1.8V/ cell
4. No power factor added
Model |
Volts |
300VA |
500VA |
1KVA |
2KVA |
3KVA |
5KVA |
7.5KVA |
10KVA |
15KVA |
20KVA |
SJ6V4.5Ah |
48V |
17 |
7 |
|
|
|
|
|
|
|
|
96V |
46 |
23 |
7 |
|
|
|
|
|
|
|
SJ6V5Ah |
48V |
28 |
14 |
|
|
|
|
|
|
|
|
96V |
62 |
35 |
1.4 |
|
|
|
|
|
|
|
SJ6V7.2Ah |
48V |
39 |
19 |
5 |
|
|
|
|
|
|
|
96V |
90 |
49 |
19 |
5 |
|
|
|
|
|
|
SJ6V10Ah |
48V |
62 |
31 |
8.5 |
|
|
|
|
|
|
|
96V |
140 |
78 |
31 |
8.5 |
|
|
|
|
|
|
SJ6V12Ah |
48V |
72 |
38 |
15 |
|
|
|
|
|
|
|
96V |
170 |
92 |
38 |
15 |
6.6 |
|
|
|
|
|
SJ12V4.2Ah |
48V |
17 |
7 |
|
|
|
|
|
|
|
|
96V |
46 |
23 |
7 |
|
|
|
|
|
|
|
SJ12V5Ah |
48V |
28 |
14 |
|
|
|
|
|
|
|
|
96V |
62 |
35 |
1.4 |
|
|
|
|
|
|
|
SJ12V7Ah |
48V |
39 |
19 |
5 |
|
|
|
|
|
|
|
96V |
90 |
49 |
19 |
5 |
|
|
|
|
|
|
SJ12V18Ah |
48V |
|
61 |
22 |
5.6 |
|
|
|
|
|
|
96V |
|
|
61 |
22 |
10 |
|
|
|
|
|
SJ12V24Ah |
48V |
|
|
39 |
12 |
5 |
|
|
|
|
|
96V |
|
|
100 |
39 |
20 |
7.5 |
|
|
|
|
SM12V33Ah |
48V |
|
|
50 |
22 |
13 |
6 |
|
|
|
|
96V |
|
|
120 |
50 |
30 |
15 |
11 |
|
|
|
SM12V38Ah |
48V |
|
|
75 |
26 |
13 |
4 |
|
|
|
|
96V |
|
|
|
75 |
40 |
18 |
8.6 |
|
|
|
SM12V65Ah |
48V |
|
|
|
50 |
28 |
12 |
5 |
|
|
|
96V |
|
|
|
|
79 |
35 |
19 |
|
|
|
SM12V100Ah |
48V |
|
|
|
|
58 |
25 |
11 |
5 |
|
|
96V |
|
|
|
|
120 |
68 |
40 |
25 |
11 |
|
SM12V120Ah |
48V |
|
|
|
|
70 |
30 |
15 |
8 |
|
|
96V |
|
|
|
|
|
82 |
50 |
29 |
15 |
8 |
SM12V150Ah |
48V |
|
|
|
|
|
50 |
22 |
13 |
7 |
|
96V |
|
|
|
|
|
100 |
75 |
50 |
22 |
10 |
SM12V200Ah |
48V |
|
|
|
|
|
|
45 |
20 |
12 |
6 |
96V |
|
|
|
|
|
|
110 |
80 |
45 |
20 |
|